6ES7134-7TD00-0AB0 ET200ISP, EL-MOD., 4 AI, HART, 2-WIRE

Product Code: 6ES7134-7TD00-0AB0

Availability: In Stock

Price: $293.87
  
 
Artikelnummer 6ES7134-7TD00-0AB0
SIMATIC DP, ELECT. SUBMODULE FOR ET200ISP, 4 AI HART, 2DMU, FOR CONNECTION OF HART 2-WIRE TRANSDUCER
Input current
from supply voltage L+, max. 320 mA
Output voltage
Power supply to the transmitters
● short-circuit proof Yes
● Supply current, max. 23 mA; per channel
Power loss
Power loss, typ. 2.7 W
Analog inputs
Number of analog inputs 4
permissible input current for current input (destruction limit), max. 90 mA
Cycle time (all channels) max. 120 ms; 30 ms basic conversion time x 4 channels with 60 Hz, 50 Hz interference frequency suppression
Technical unit for temperature measurement adjustable Yes
Input ranges
● Voltage No
● Current Yes
● Thermocouple No
● Resistance thermometer No
● Resistance No
Input ranges (rated values), currents
● 4 to 20 mA Yes
Cable length
● Cable length, shielded, max. 500 m
Analog value generation
Measurement principle integrating (Sigma-Delta)
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 13 bit
● Integration time, parameterizable No
● Interference voltage suppression for interference frequency f1 in Hz 50 / 60 Hz
Smoothing of measured values
● parameterizable Yes; in 4 stages
● Step: None Yes; 1 x cycle time
● Step: Low Yes; 4 x cycle time
● Step: Medium Yes; 32 x cycle time
● Step: High Yes; 64 x cycle time
Encoder
Connection of signal encoders
● for current measurement as 2-wire transducer Yes
— Burden of 2-wire transmitter, max. 750 Ω
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.015 %
Temperature error (relative to input range), (+/-) 0.005 %/K
Crosstalk between the inputs, min. -50 dB
Repeat accuracy in steady state at 25 °C (relative to input area), (+/-) 0.01 %
Operational error limit in overall temperature range
● Current, relative to input area, (+/-) 0.15 %
Basic error limit (operational limit at 25 °C)
● Current, relative to input area, (+/-) 0.1 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of interference < rated value of input range), min. 70 dB
Interrupts/diagnostics/status information
Alarms
● Diagnostic alarm Yes; Parameterizable
● Limit value alarm Yes; Parameterizable
Diagnostic messages
● Diagnostic information readable Yes
● Wire-break Yes
● Short-circuit Yes
Diagnostics indication LED
● Group error SF (red) Yes
Galvanic isolation
Galvanic isolation analog inputs
● between the channels No
● between the channels and the backplane bus Yes
Standards, approvals, certificates
CE mark Yes
Highest safety class achievable in safety mode
● acc. to IEC 61508 none
● Performance level according to EN ISO 13849-1:2008 none
Use in hazardous areas
● Type of protection acc. to EN 50020 (CENELEC) II2 G (1) GD Ex ib[ia] IIC T4 and I M2 Ex ib[ia] I
● Type of protection acc. to KEMA 04 ATEX 1244
Dimensions
Width 30 mm
Height 129 mm
Depth 136.5 mm
Weights
Weight, approx. 230 g
last modified: 21.08.2014

Write a review

Note: HTML is not translated!

Rating: Bad Good

Enter the code in the box below: