6ES7322-5FF00-0AB0 SM322, 8DO, AC120/230V, 2A

Product Code: 6ES7322-5FF00-0AB0

Availability: In Stock

Price: $174.68
  
 
Artikelnummer 6ES7322-5FF00-0AB0
SIMATIC S7-300, DIGITAL OUTPUT SM 322, OPTICALLY ISOLATED, 8 DO, 120/230V AC, 2A, WITH 1 POINT PER COMMON AND SELECTABLE FAIL MODE, 1 X 40 PIN
Supply voltage
Load voltage L1
● Rated value (AC) 230 V; 120/230 V AC
● permissible range, lower limit (AC) 79 V
● permissible range, upper limit (AC) 264 V
Input current
from load voltage L1 (without load), max. 2 mA
from backplane bus 5 V DC, max. 100 mA
Power losses
Power loss, typ. 8.6 W
Digital outputs
Number of digital outputs 8
Switching capacity of the outputs
● Lamp load, max. 50 W
Output voltage
● for signal "1", min. L1 (-8.5 V)
Output current
● for signal "1" rated value 2 A
● for signal "1" permissible range for 0 to 40 °C, max. 2 A
● for signal "1" minimum load current 10 mA
● for signal "1" permissible surge current, max. 20 A; with 2 half waves
● for signal "0" residual current, max. 2 mA
Switching frequency
● with resistive load, max. 10 Hz
● with inductive load, max. 0.5 Hz
● on lamp load, max. 1 Hz
Aggregate current of outputs (per group)
horizontal installation
— up to 40 °C, max. 8 A
— up to 60 °C, max. 4 A
vertical installation
— up to 40 °C, max. 4 A
Cable length
● Cable length, shielded, max. 1 000 m
● Cable length unshielded, max. 600 m
Interrupts/diagnostics/status information
Alarms
● Diagnostic alarm Yes; Parameterizable
Diagnostic messages
● Diagnostics Yes
Galvanic isolation
Galvanic isolation digital outputs
● between the channels, in groups of 1
● between the channels and the backplane bus Yes; Optocoupler
Isolation
Isolation checked with 1500 V AC
Connection method
required front connector 40-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 120 mm
Weights
Weight, approx. 275 g
last modified: 08.09.2014