6ES7323-1BH01-0AA0 SM323, 8DI/8DO, DC24V, 0,5A

Product Code: 6ES7323-1BH01-0AA0

Availability: In Stock

Price: $149.33
  
 
Artikelnummer 6ES7323-1BH01-0AA0
SIMATIC S7-300, DIGITAL MODULE SM 323, OPTICALLY ISOLATED, 8 DI AND 8 DO, 24V DC, 0.5A AGGREGATE CURRENT 2A, 1X20 PIN
Supply voltage
Load voltage L+
● Rated value (DC) 24 V
● permissible range, lower limit (DC) 20.4 V
● permissible range, upper limit (DC) 28.8 V
Input current
from load voltage L+ (without load), max. 40 mA
from backplane bus 5 V DC, max. 40 mA
Power losses
Power loss, typ. 3.5 W
Digital inputs
Number of digital inputs 8
Input characteristic curve in accordance with IEC 61131, type 1 Yes
Number of simultaneously controllable inputs
all mounting positions
— up to 40 °C, max. 8
— up to 60 °C, max. 8
Input voltage
● Type of input voltage DC
● Rated value, DC 24 V
● for signal "0" -30 to +5 V
● for signal "1" 13 to 30 V
Input current
● for signal "1", typ. 7 mA
Input delay (for rated value of input voltage)
for standard inputs
— at "0" to "1", min. 1.2 ms
— at "0" to "1", max. 4.8 ms
— at "1" to "0", min. 1.2 ms
— at "1" to "0", max. 4.8 ms
Cable length
● Cable length, shielded, max. 1 000 m
● Cable length unshielded, max. 600 m
Digital outputs
Number of digital outputs 8
short-circuit protection Yes
● Response threshold, typ. 1 A
Limitation of inductive shutdown voltage to L+ (-53 V)
Controlling a digital input Yes
Switching capacity of the outputs
● Lamp load, max. 5 W
Load resistance range
● lower limit 48 Ω
● upper limit 4 kΩ
Output voltage
● for signal "1", min. L+ (-0.8 V)
Output current
● for signal "1" rated value 0.5 A
● for signal "1" permissible range for 0 to 60 °C, min. 5 mA
● for signal "1" permissible range for 0 to 60 °C, max. 0.6 A
● for signal "1" minimum load current 5 mA
● for signal "0" residual current, max. 0.5 mA
Output delay with resistive load
● "0" to "1", max. 100 µs
● "1" to "0", max. 500 µs
Parallel switching of 2 outputs
● for increased power No
● for redundant control of a load Yes; only outputs of the same group
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 0.5 Hz
● on lamp load, max. 10 Hz
Aggregate current of outputs (per group)
horizontal installation
— up to 40 °C, max. 4 A
— up to 60 °C, max. 4 A
Cable length
● Cable length, shielded, max. 1 000 m
● Cable length unshielded, max. 600 m
Encoder
Connectable encoders
● 2-wire sensor Yes
— Permissible quiescent current (2-wire sensor), max. 2 mA
Isochronous mode
Isochronous operation (application synchronized up to terminal) No
Interrupts/diagnostics/status information
Alarms
● Alarms No
Diagnostic messages
● Diagnostic functions No
Diagnostics indication LED
● Status indicator digital output (green) Yes
● Status indicator digital input (green) Yes
Galvanic isolation
Galvanic isolation digital inputs
● between the channels Yes
● between the channels, in groups of 8
● between the channels and the backplane bus Yes; Optocoupler
Galvanic isolation digital outputs
● between the channels Yes
● between the channels, in groups of 8
● between the channels and the backplane bus Yes; Optocoupler
Permissible potential difference
between different circuits 75 VDC / 60 VAC
Isolation
Isolation checked with 500 V DC
Connection method
required front connector 20-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 120 mm
Weights
Weight, approx. 220 g
last modified: 08.09.2014